Boards Home > Signal Conditioning & Power Modules-SG-3013
Isolated RTD input module
» Features
¡á 3000Vdc isolation (three-way)
¡á Wide input/output range
¡á Stable voltage or current output
¡á Easy to configure input/output range
¡á Two VRs for calibrating accuracy of the input/ output range
¡á Flexible DIN-rail mounting
¡á LED Indicator
» Functional Description
The SG-3013 is a RTD input to voltage or current output signal conditioning module.
It has 3000Vdc three-way isolation for input, output and power.
It also can change the input/output range via internal configuration switches.
The SG-3013 has an LED display to show whether the SG-3013 is functioning correctly and has two VRs (Zero, Span) to calibrate the accuracy of the input/output range.
The bandwidth of the SG-3013 is typically 5.24KHz.
It's easy to mount the SG-3013 on a standard DIN rail and can operate in environments with wide temperature range.
» Applications
¡Ü Input/output signal conditioning
¡Ü Input, output or power isolation
» Specifications Signal Input
¡Ü Input Type : Pt-100, Pt-1000, Ni 120
¡Ü Temperature Range : Pt100 ¥á=0.00385, -100¡ÆC~+600¡ÆC
Pt100 ¥á=0.003916, -100¡ÆC~+600¡ÆC
Ni 120, -80¡ÆC~+100¡ÆC,
Pt1000 ¥á=0.00385, -200¡ÆC~+600¡ÆC
¡Ü Input Connections : 2/3/4 wires
Voltage Output
¡Ü Bipolar : ¡¾10V
¡Ü Unipolar : 0~5V, 0~10V
¡Ü Output impedance : <50¥Ø Current Output
¡Ü Current : 0~20mA, 4~20mA
¡Ü Current load resistance : 0~500¥Ø (Source) Supply Voltage
¡Ü Input Range : 10~30Vdc
¡Ü Consumption : 2W General Specifications
¡Ü Three-way isolation : 3000Vdc
¡Ü Accuracy : ¡¾0.1% of full range
¡Ü Operation bandwidth : 5.24KHz
¡Ü Operating temperature : -25¡ÆC ~ 75¡ÆC
¡Ü Storage temperature : -30¡ÆC ~ 85¡ÆC
¡Ü Weight : 105 grams
¡Ü Dimensions : 113mm x 70.5mm x 24.5mm
Block Diagram
Ordering Information Standard SG-3013 : Isolated RTD input module